Part Number Hot Search : 
102M35 102M35 MAX40 TDA21 DMRBA TB772 SKY65 C47TM10
Product Description
Full Text Search
 

To Download PMP25 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 PMP 25
Rectifier Module
Description
The Power-One PMP 25 rectifier uses resonance switch mode technology (soft switching), and incorporates thermal protection while providing extremely reliable DC power in a small space. Rectifier communication is accomplished using digital interfaces over an RS485 data bus. Information is transmitted to adjacent rectifiers while providing status and identification information to the system controller (PCS). At only 4 rack units high, these compact rectifiers allow for up to five modules in each 23in. rack (4 units in 19in. rack) providing up to 250A at 48V or up to 550A at 24V. With full power available up to 65C, PMP 25 rectifiers are ideal for any indoor or outdoor application.
Features
* Compact 4 rack-unit height * 50A output at 48V * 110A output at 24V * 208 / 240 single phase input * Input over-voltage disconnect * Hot-swappable rectifiers * High efficiency, up to 91% * Active current sharing * International standards compliance
PPS 25 System Shown
www.power-one.com
PMP 25
Rectifier Module
Input
Model Input Voltage Current (max.) Soft Start Harmonics Surge Immunity Fuse Connection EMC PMP 25.24 PMP 25.48 196 - 250V AC 10% single phase, (44-66Hz) 176-160V AC at reduced output power <22A <22A <20A <20A
Mechanical
Dimensions Weight Cooling Interface 105 x 176 x 455mm (6.9 x 4.13 x 17.9in.) 6.2kg (13.6lbs.) Fan: speed controlled and monitored RS485 for communication with the supervision module Reinforced insulation tested at: 4.25 kV DC primary-secondary, 2.12 kV DC primary-ground, 0.75 kV DC secondary ground IP20 In 19"/ 4U subrack up to 4 In 23"/ 4U subrack up to 5
EN 61000-3-2 Power Factor >0.98 at 50-100% load EN 61000-4-5 F 25A Harting MH - 21 Signal pins, 3 HC pins EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Insulation
Enclosure Mounting
Other Technical Data
Safety EN 60950 CSA C22-2 No. 950, UL 1950 Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75C with automatic restart.* Input over-voltage disconnection at >275VAC with automatic reset at >260VAC. Green LED Power ON Thermal Protection Comm. Error Module Failure
Output
Model Power (max.) Output Voltage Current (max.) Efficiency
(@ 40-90%Load)*
PMP 25.24 3080W 22-30V DC 110A >89% Vout +/- 0.5%
PMP 25.48 2800W 44-58V DC 50A >91% Protection
Tolerance Transient Response Load Sharing Ripple Psophometric Connection EMC
Yellow LED Indications Yellow Flashing Red LED Audible Noise Operating Temperature* Storage Temperature Radiated EMC <60dBA 48V: -25 to +60C 24V: -40 to +65C -40 to +85C
+/- 6% at load variation 10-90% or 90-10%, recovery time 150ms <5% of nominal current <100mV p-p (BW. 30MHz) <2mV, according to CCITT norms 8mm HC-pins EN 61000-6-2, EN 61000-6-4
EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3
* Average performance for a single rectifier
Environment
Note: All specifications are subject to change without notification.
11V0005-029 PMP 25 V3.0
www.power-one.com


▲Up To Search▲   

 
Price & Availability of PMP25

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X